Small & Medium Hospital (IEC) 300-Bed - Summary
IEC Electrical & Digital Architectures of reference for Hospital
Published by
Schneider Electric

Small & Medium Hospital (IEC) 300-Bed - Summary
Published by
Schneider Electric
Free
Overview
Reusable Reference Design for IEC Medium Hospital building
The Hospital digital electrical distribution reference design is based on the IEC 60364-7-710 standard for medical location recommendation dealing with Groups 2, 1 and 0 as medical locations with 0,5s; 15s; over 15s energy availability requested performance, respectively.
The single line diagram is composed of an N+1 diesel generator and UPS backup systems and a 2N path to maximise the energy availability performance and to optimise CAPEX.
Digitisation reinforces continuity of service with monitoring and remote-control systems, reduces electrical shock with IT network power supply for operating wards and reduces fire risks thanks to thermal monitoring in MV/LV switchgear or arc fault detection devices in distribution boards. Digitisation also improves operational efficiency through condition based maintenance reporting.
Note: This offer contains only Engineering Reports. For full offer with CAD files please see Full Engineering Package in Related offers.
Reusable Reference Design for IEC Medium Hospital building
The Hospital digital electrical distribution reference design is based on the IEC 60364-7-710 standard for medical location recommendation dealing with Groups 2, 1 and 0 as medical locations with 0,5s; 15s; over 15s energy availability requested performance, respectively.
The single line diagram is composed of an N+1 diesel generator and UPS backup systems and a 2N path to maximise the energy availability performance and to optimise CAPEX.
Digitisation reinforces continuity of service with monitoring and remote-control systems, reduces electrical shock with IT network power supply for operating wards and reduces fire risks thanks to thermal monitoring in MV/LV switchgear or arc fault detection devices in distribution boards. Digitisation also improves operational efficiency through condition based maintenance reporting.
Note: This offer contains only Engineering Reports. For full offer with CAD files please see Full Engineering Package in Related offers.
The single line diagram is composed of an N+1 diesel generator and UPS backup systems and a 2N path to maximise the energy availability performance and to optimise CAPEX.
Digitisation reinforces continuity of service with monitoring and remote-control systems, reduces electrical shock with IT network power supply for operating wards and reduces fire risks thanks to thermal monitoring in MV/LV switchgear or arc fault detection devices in distribution boards. Digitisation also improves operational efficiency through condition based maintenance reporting.
Note: This offer contains only Engineering Reports. For full offer with CAD files please see Full Engineering Package in Related offers.